Category
Single Cabinet(18K)/ Dual Cabinets(36K)/ Three Cabinets(54K)
Dimensions (w*d*h)
2250*1400*2200mm/ 3000*1400*2200mm/ 3750*1400*2200mm
Number of Immersion Liquid Cooling IT cabinets
1 / 2 /3
Power of Immersion Liquid Cooling IT cabinets (kW)
18
Computing units supported by Immersion Liquid Cooling IT cabinets (units)
4
Power supply format of Immersion Liquid Cooling IT cabinets
Dual 63A/380VAC
Number of network cabinets (air-cooled)
1
Power of network cabinets (air-cooled) (kW)
6 / 6 /10
Power supply format of network cabinets (aircooled)
Dual 32A/220VAC / Dual 32A/220VAC / Dual 63A/220VAC
Static weight
2.0t / 2.8t / 3.6t
Refrigeration system
Row AC + external chiller (power distribution and network), distributed CDM (IT cabinet) + external chiller
Cabinet (optional)
Single-opening glass front door, driving ring screen, double-opening steel plate rear door
Rack-mounted modular UPS (optional)
20-100kVA Capacity,3-Phase lo (N+1 Power Module Redundancy)
Backup battery (optional)
15min (immersion lithium battery/lead acid)
Power distribution module
Integrated power distribution PDU
Cable routing
Up in and up out / Down in and down out
Noise
≤52dB
Fire protection module (optional)
Rack mounted gas fire extinguishing device, temperature controlled, heptafluoropropane/perfluoroacetone
Infrastructure Monitoring
7-inch touch screen, temperature and humidity, smoke, lightning protection,total voltage, total current, total power, total energy, PUE, sound and light alarm, etc.