System parameters |
Battery type |
LFP 3.2V/280Ah |
Cycle life |
≥ 6500 times (25 ℃ ±5 ℃ / 100% DOD swap 80% energy retention) |
System rated energy (kWh) |
233 | 261 |
Voltage sampling point layout ratio |
1:1 |
Temperature sampling point layout ratio |
1:1 |
Battery voltage range (V) |
600~950 |
BMS equilibrium mode |
Active equilibrium |
Discharge depth (DOD) |
100% |
Ac side parameters |
Rated voltage range (V) |
380±15% |
Rated frequency range (Hz) |
50/60±2.5 |
Adjustable range of power factor |
-1~+1 |
THDi |
<3% |
Parallel / offline function |
Support |
Ac side power rating (kw) |
120 | 150 |
Other parameters |
Ambient temperature range (°C) |
-20~+50 |
Relative humidity range |
0-95% (no condensation) |
Communication interface |
RS485/LAN/4G |
Peak system efficiency |
90% |
Protection grade |
IP55(PCS IP65) |
Noise (dB) |
<55 |
Thermal management technology |
Plate exchange liquid cooling |
Fire fighting system |
Kechuang special fire fighting gas + PACK fire fighting + active early warning |
System combination |
233×N(1≤N≤10) / 261×N(1≤N≤10) |
Dimension WxDxH (mm) |
1400×1400×2300 |
Weight (t) |
2.8 |